LI-PAC Load Interrupter Switchgear
Code:  LI
INTRODUCTION
  Olsun Electrics load interrupter switchgear provides a reliable and safe method of switching as well as overcurrent protection for primary feeders.  Load Interrupter Switches can be supplied as Stand Alone Units, Multiple Section Lineups, or as an option with Olsun unit substation transformers.
  Olsun’s flexible engineering and manufacturing capabilities can provide custom designed switchgear to fit most applications. 
  Switches are UL/CSA Listed thru 600 Amp, 15kV, in both NEMA 1 and NEMA 3R Construction
RATINGS
5kV  200 Amperes
60kV BIL
60 Hz
Momentary (AMPS ASYM) 20,000
Fault close (AMPS ASYM) 20,000
Short Time 1sec (AMPS SYM) 12,500
Low Frequency withstand 19kV
15kV  600 Amperes
95kV BIL
60 Hz
Momentary (AMPS ASYM) 40,000
Fault close (AMPS ASYM) 40,000
Short Time 2 sec (AMPS SYM) 25,000
Low Frequency withstand 36kV
STANDARD FEATURES
OPTIONAL FEATURES
1. NEMA 1 indoor enclosure
2. Switch viewing window
3. Mechanically interlocked fuse 
access door
4. Plated terminals
5. Structural steel welded base
6. Easily Accessible Terminals
7. Internal ground bus
1. Current Limiting Fuses or Power Fuses
2. NEMA 3R or NEMA 4 enclosures
3. Cable compartment
4. Lightning arresters
5. Current transformers
6. Key interlocks
7. Multiple switch line up
Also Available thru 38kV, 1200 Amp

© Copyright 2003 by Olsun Electrics Corporation & Web Centers of America, Inc. All rights reserved